Connecting and disconnecting the refrigerant circuit pipes to the compressor
Note: Evacuate the refrigerant using an air conditioning service stand. After disconnecting, close the refrigerant lines and compressor connections with plugs to protect against moisture from the air.

1. 23 Nm
2. High pressure pipeline connection nipple; anti-rotation protection with centering sleeve
3. Low pressure pipeline connection nipple: anti-rotation protection with centering sleeve
4. O-ring (low pressure circuit)
5. Centering sleeve
6. Groove for sealing ring
7. O-ring with circular cross-section (high pressure circuit)
Information published on the website [SkodaBook.ru]
Connecting and disconnecting the refrigerant circuit pipes to the condenser
Note: After removal, seal the refrigerant lines and condenser connections with suitable plugs to prevent moist air from entering.

1. Screws, 10 Nm
2. Refrigerant pipeline
3. Sealing rings
3. Refrigerant line nipple: anti-rotation protection with centering sleeve
4. Condenser nipple